Emerson SI-DeviceNet User Manual page 35

Table of Contents

Advertisement

Input cyclic mapping length
S.01.020
Output cyclic mapping length
S.01.021
Pr S.01.020 and Pr S.01.021 indicate the current mapping length used for sending and
receiving data.
To set a different value for the mapping lengths, refer to Pr S.01.018 and Pr S.01.019.
Input mapping status
S.01.022
Output mapping status
S.01.023
If the DeviceNet Network Diagnostic parameter (Pr S.01.006) indicates "Init Failed", a
mapping configuration error has been could have been detected. The reason for the
error is indicated by the SI-DeviceNet input mapping status parameter (Pr S.01.022)
and the SI-DeviceNet output mapping status parameter (Pr S.01.023).
When a mapping error has been corrected, reset the SI-DeviceNet module by setting
Pr S.01.002 or MM.007 to On (1).
SI-DeviceNet User Guide
Issue Number: 2
Default
4
Range
0 to 28
Access
RO
Default
4
Range
0 to 28
Access
RO
Default
N/A
Range
No error (0) to Reserved (10)
Access
RO
Default
N/A
Range
No error (0) to Reserved (10)
Access
RO