Reset module
S.00.007
Changes to the SI-DeviceNet configuration will not take effect until the SI-DeviceNet
has been reset.
To reset the SI-DeviceNet:
Set Pr S.00.007 to On (1).
When the sequence has been completed, Pr S.00.007 will be reset to Off (0).
The SI-DeviceNet will reset using the updated configuration.
This sequence does NOT store the SI-DeviceNet configuration parameters in the drive
NOTE
or the SI-DeviceNet flash memory. This parameter will change back to Off immediately,
and as such the change may not be visible on the display.
Default DeviceNet Interface
S.00.008
If the host drive is defaulted (see the drive user guide for details), it will also clear the
current configuration for the slot SI-DeviceNet is installed to.
This can be performed as follows:
Set Pr S.00.008 to On (1).
Reset the module by setting Pr S.00.007 to On (1).
SI-DeviceNet communications will be stopped.
Default parameter values for the SI-DeviceNet will be loaded.
The SI-DeviceNet will reset using the default values.
SI-DeviceNet User Guide
Issue Number: 2
Default
Off (0)
Range
Off (0) or On (1)
Access
RW
Default
Off (0)
Range
Off (0) or On (1)
Access
RW