3.6
SCL/SCM Control Wiring Diagrams
3.6.1
SCL/SCM Terminal Strip
Shown below is the control terminal strip, along with a brief description of the function of each
terminal. The following wiring diagram examples provide a quick reference to wire the drive for the
most common configurations.
1
2
5
+
-
Maintained
RUN/STOP
Contact
SCL/SCM Terminal Strip
NOTE
•
The function of terminals TB-13A, 13B, 13E and the Form A relay at terminals 16
and 17 are dependent on the programming of certain parameters.
Refer to Section 4.4 Description of Parameters.
•
The digital inputs (terminals 1, 13A, 13B, and 13E) are active-high. They can
be activated using terminal 11 (which is +12 VDC) as shown in the following
diagrams, or by using an external voltage source with a range of +12 VDC to +28
VDC (+ 10%).
Lenze 13466147 EDBSM01 v19 EN
6
11
13A
13B
Installation
13E
25
+
FORM A RELAY
17
16
3
21