Description Of Parameters - Lenze SM004S Operating Instructions Manual

Scl series; scm series
Table of Contents

Advertisement

4
Commissioning
4.4

Description of Parameters

P01
LINE VOLTAGE SELECTION
Parameter P01 calibrates the drive for the actual applied input voltage. Set this parameter to HIGH
(01) for 120, 220-240, and 460-480 Vac input, or LOW (02) for 200-208 and 380-415 Vac input.
NOTE
If this parameter is changed while the drive is running, the new value will not take effect
until the drive is stopped.
P02
CARRIER FREQUENCY
Parameter P02 sets the switching rate of the output IGBT's. Increasing the carrier frequency will result
in less audible motor noise. Available settings are: 4 kHz, 6 kHz, 8 kHz, and 10 kHz.
Parameter
Setting
Frequency
01
02
03
04
NOTE
The SCL/SCM drive is fully rated up to 8 kHz carrier frequency. If the 10 kHz carrier
frequency is selected, the drive's ambient temperature rating OR output current
rating must be de-rated to the value shown in the table above.
If this parameter is changed while the drive is running, the change will not take
effect until the drive is stopped.
P03
START METHOD
WARNING!
Automatic starting of equipment may cause damage to equipment and/or injury to
personnel! Automatic start should only be used on equipment that is inaccessible to
personnel.
01
NORMAL: The drive will start when the appropriate contact is closed on the terminal strip.
Refer to Section 3.6 for possible control configurations.
02
START ON POWER UP: The drive will automatically start upon application of input power.
03
START WITH DC BRAKE: When a START command is given, the drive will apply DC BRAKE VOLTAGE
(Parameter 22) for the duration of DC BRAKE TIME (Parameter 21) prior to starting the motor
to ensure that the motor is not turning.
34
Carrier
or Output Derate
4 kHz
40°C or 100%
6 kHz
40°C or 100%
8 kHz
40°C or 100%
10 kHz
35°C or 92%
Ambient
Lenze 13466147 EDBSM01 v19 EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents