3.2.3

Input Wire Size Requirements

120 Vac 1 phase
Model
AWG mm
SM004S
14
2.5
SM005S
14
2.5
SM010S
12
4.0
SM015S
10
6.0
3.2.4

Installation According to EMC Requirements

The SCM and SCL Series can be installed to meet the European standards for Electromagnetic
Compatibility (EMC) requirements. These requirements govern the permissible electromagnetic
emissions and immunity, both radiated and conducted, of a drive system.
The EMC requirements apply to the final installation in its entirety, not to the individual components
used. Because every installation is different, the recommended installation should follow these
guidelines as a minimum. Additional equipment (such as ferrite core absorbers on power conductors)
or alternative wiring practices may be required to meet conformance in some installations.
Filter: The input to the drive (or group of drives) must include a filter to reduce the electrical noise
reflected back to the AC Line. The SCL Series includes a filter that has been tested to meet the industrial
standards set by the EU, EN 61800-3 for conducted emissions and EN 55011 for radiated emissions
to class A compliance when installed in a control cabinet with a motor cable < 10m. The SCM can be
installed to meet these same standards when used with an appropriately installed external line filter.
EMC
Compliance with EN 61800-3/A11
Installation: Shielded cable must be used for all control and power cables
and exposed wiring must be kept as short as possible.
A
Screen clamps
B
Control cable
C
Low-capacitance motor cable
(core/core < 75 pF/m, core/screen < 150 pF/m)
D
Electrically conductive mounting plate
E
Filter
Lenze 13466147 EDBSM01 v19 EN
Input Wire Size Requirements
208/240 Vac 1 phase
2
Model
AWG mm
S_204S
14
S_205S
14
S_208S
14
S_210S
14
S_215S
14
S_220S
12
S_230S
10
208/240 Vac 3 phase
2
Model
AWG mm
2.5
2.5
SM205
14
2.5
2.5
SM210
14
2.5
SM215
14
4.0
SM220
14
6.0
SM230
14
SM250
12
SM275
8
SM2100
8
SM2150
6
Installation
400/480 Vac 3 phase
2
Model
AWG mm
2.5
SM405
14
2.5
SM410
14
2.5
SM415
14
2.5
SM420
14
2.5
SM430
14
4.0
SM450
14
10
SM475
12
10
SM4100
10
16
SM4150
8
B
E
C
D
A
SM01-1
3
2
2.5
2.5
2.5
2.5
2.5
2.5
4.0
6.0
10
15