Two-Wire Start/Stop Control

1
2
5
+
-
Maintained
RUN/STOP
Contact
(FORWARD)
2-Wire Start/Stop Control
NOTE
Close TB-1 to TB-11 to RUN, and open to STOP. TB-1 functions as a RUN input for
two-wire start/stop circuits, and a STOP input for three-wire start/stop circuits.
Refer to Section 3.6.3
If reverse direction is required, set ROTATION (Parameter 17) to FORWARD AND
REVERSE (02), and program TB-13A (Parameter 10) to RUN REVERSE (06). Close
TB-13A to TB-11 to RUN in the reverse direction, and open to STOP.
For 0-10 VDC or 4-20 mA speed control, set STANDARD SPEED SOURCE
(Parameter 05) to 0-10 VDC (03) or 4-20 mA (04).