All brand names mentioned in this documentation are trademarks of their corresponding owners. Tip! Detailed information about POWERLINK can be found on the website of the Ethernet POWERLINK Standardization Group: www.ethernet-powerlink.org Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 5
Engineering tools installed (e.g. »Engineer«), the screenshots in this documentation may deviate from the actual screen representation. Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Optically highlighted reference to another page. Can be activated with a mouse-click in this documentation. Step-by-step instructions Step-by-step instructions are indicated by a pictograph. Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
The Managing Node accepts the control function for the data communication of the decentralised field devices. Typically, the Managing Node is the communication interface of a PLC. Node ID EPL node address Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Application notes Pictograph Signal word Meaning Note! Important note to ensure trouble-free operation Tip! Useful tip for easy handling Reference to another document Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
( 13) • The specifications, processes, and circuitry described in this document are for guidance only and must be adapted to your own specific application. Lenze does not take responsibility for the suitability of the process and circuit proposals. • Only qualified personnel may work with and on Lenze drive and automation components. In accordance with IEC 60364 and CENELEC HD 384, these are persons ...
Observe the safety instructions and application notes contained in this manual. Residual hazards Device protection The Communication Unit contains electronic components that can be damaged or destroyed by electrostatic discharge. ( 18) Installation Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
• can only be used in POWERLINK networks. • can also be used without being connected to the POWERLINK network. Any other use shall be deemed inappropriate! Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
• Up to 6 data words (max. 12 bytes) can be sent or received. • Very short CN response times for optimal network performance • Communication with the Lenze »EASY Starter« (access to all Lenze parameters) is executed via the diagnostic interface of the Drive Unit.
Plug connector for wiring the POWERLINK IN to A2 Plug connector for wiring the POWERLINK OUT to A3 Plug connector for wiring the LEDs at A1 Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 15
X3, X4 and X61. Hardware manual for the Inverter Drive 8400 motec Observe the notes and wiring instructions contained in this documentation. Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
• U = 24 V DC (20 V - 0 % ... 29 V + 0 %) • I = 120 mA Conformities, approvals • CE • UR / cUR • EAC (see also hardware manual) Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Some codes may require a longer processing time (see reference manual/ online help for Inverter Drive 8400 motec). process data There are no interdependencies between parameter data and Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
• Fieldbus communication is not possible or faulty. • I/O signals are faulty. • The safety function is faulty. Protective measures Discharge electrostatic charges before touching the Communication Unit. Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Legend for Fig. [5-1] Drive Unit Communication unit Wiring Unit Cover of the Drive Unit EDK84DG... Mounting instructions of the Drive Unit, Communication Unit, Wiring Unit Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Both sizes reduce the real-time capability and dynamics. The cable length between both nodes is limited to 100 m. Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 21
• Observe the restrictions of the used managing node. Managing Node 1. CN group 2. CN group E94YCEP033 [5-3] Star topology for 1 to 2 CN groups Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
2. No operation with real-time EPL must be carried out. No integration of a managing node (EPL address = 240) into the standard Ethernet network. Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Tx + Data line (transmitted data, plus) Rx + Data line (received data, plus) Tx - Data line (transmitted data, minus) Data line (received data, minus) Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
• Access to parameters of a device that is disconnected from the mains is not possible. Hardware manual for the Inverter Drive 8400 motec Here you can find detailed information on how to wire the Communication Unit. Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Before initial switch-on Stop! Before switching on the inverter for the first time, check the entire wiring with regard to completeness, short circuit, and earth fault. Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
• In case of the following DIP switch settings, the node ID is obtained from C13899: • DIP1, switch 1 is "ON" • DIP1, switch 1 is "OFF" and DIP2, switch 1 ... 8 are "OFF" (Lenze setting). • The node IDs must differ from each other in case of several networked POWERLINK nodes.
Page 27
• In C13864, the active node ID is displayed. • C13865 displays whether the node ID has been set via DIP switches or via C13899. Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
( 24) • Addressing can be carried out manually via DIP switches or codes in the »EASY Starter«/ »Engineer«. Node address (node ID) setting ( 26) Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
C13899 Node ID SW Setting of the node ID, unless a node ID is set via DIP switches. C13920 Current address switch Read only Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
3. Open the fieldbus diagnostics dialog window via the button. • The dialog box displays the codes you can use to make the POWERLINK settings. Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 31
0x1001 error memory Read only C13110 SoC Cycle Counter Read only C13136 0x1F8C NMT Communica- Read only tion Status C13861 Emergency data load Read only C13867 Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
( 22) 0x1F99 object (NMT_CNBasicEthernetTimeout_U32) must be higher than the value of the 0x1F89 object (NMT_BootTime_REC) which is the case by default. Index table ( 62) Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
• Process data are not saved in the Inverter Drive 8400 motec. • Process data are e.g. setpoints, actual values, control words, and status words. Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
2. Select the port blocks MCI_IN or MCI_OUT on the Ports tab with a mouse-click and activate them with the Activate () button. 3. Click the Edit port ... () button. Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 35
Signal assignment --> Function block dialog box. • Select the desired signals. • Confirm the selection with OK. Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 36
• Confirm the selection with OK. 6. Set the control mode to "Network (MCI/CAN)" (C00007 = 40) on the Application parameter tab. Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
• The Communication Unit reports interrupted communication via an emergency telegram to the master and changes to the "Safe-Operational" state. • The error message "EPL: Lost connection to 8400 target [0x01bc3100]" is output. ( 42) Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
200 ms EPL node is in the "Stopped" status (waiting for disconnection). EPL status: NMT_CS_STOPPED EPL node is in the operating phase. EPL status: NMT_CS_OPERATIONAL Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 39
(Standard device is switched off, initialising or not present.) No error A fieldbus error has occurred (POWERLINK collision). Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
0x0001 29 ... 32 Error code Reference manual/online help for the Inverter Drive 8400 motec Detailed information on the error codes is provided here. Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
No reaction System fault Fault Trouble Quick stop by trouble WarningLocked Warning Information Cause Remedy Communication unit is defective. Send Communication Unit with error description to Lenze. Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 43
No reaction System fault Fault Trouble Quick stop by trouble WarningLocked Warning Information Cause Remedy Access to parameter set in memory module via standard Download application again (including module). device was not successful. Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 44
• A device in the network is not EPL-compliant. • Reduce EMC interference on the network or use an additional shield connection. • EMC interference is too strong. Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
• Lenze setting (hex): 0xC0A864FE = 192.168.100.254 Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 47
• xx-yy-zz = consecutive number Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 48
The managing node sends PRes frames 13 ... 30 Reserved / No function 31 (MSB) Bits 0 ... 30 inhibited Bits 0 ... 30 enabled Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 49
The managing node sends PRes frames 13 ... 30 Reserved / No function 31 (MSB) Bits 0 ... 30 inhibited Bits 0 ... 30 enabled Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 50
No "POWERLINK to fieldbus" router function. The device can be used as an "POWERLINK to fieldbus" router (router type 1). 14 ... 31 Reserved / No function (MSB) Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 51
19000 19000 20000 20000 Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 52
Byte 1490 36 bytes Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 53
μs 4294967295 5000000 μs Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 54
0x1A00.0 Number of mapped Tx PDO-1 Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 55
(min. value | unit | max. value) Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 56
Bit 0 CU Synchronisation is locked if TRUE Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 57
• digits (0 ... 9); • hyphen (-). Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 58
Display of the version number of the Communication Unit firmware. Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 59
(min. value | unit | max. value) Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 66
POWERLINK error messages Causes and remedies Feedback to Lenze Short overview Firmware Date (C13901) Process data Firmware Type (C13900) Process data transfer Firmware Version (C13902) Processing time Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Page 67
Technical data Terminology used Terms Total cycle times TPDO user data per application Transmission mode Type of node Validity of the documentation Versions Voltage supply Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018...
Perhaps we have not succeeded in achieving this objective in every respect. If you have suggestions for improvement, please e-mail us feedback-docu@lenze.com Thank you very much for your support. Your Lenze documentation team...
Need help?
Do you have a question about the POWERLINK E84DGFCL Series and is the answer not in the manual?
Questions and answers