3.6.3
Three-Wire Start/Stop Control
1
2
5
-
+
Momentary
STOP
Contact
3-Wire Start/Stop Control
NOTE
•
Program TB-13E (Parameter 12) for START FORWARD (06).
•
If reverse direction is required, set ROTATION (Parameter 17) to FORWARD AND
REVERSE (02), and program TB-13A (Parameter 10) for START REVERSE (07).
•
Momentarily close TB-13E to TB-11 to START in the forward direction, or close TB-
13A to TB-11 to START in the reverse direction. Momentarily open TB-1 to TB-11
to STOP the drive.
•
For 0-10 VDC or 4-20 mA speed control, set STANDARD SPEED SOURCE
(Parameter 05) to 0-10 VDC (03) or 4-20 mA (04).
Lenze 13466147 EDBSM01 v19 EN
11
13B
6
13A
REV
Momentary
START
Contact
Installation
13E
25
+
FWD
FORM A RELAY
17
16
3
23