Commissioning

4.1

Initial Power-Up and Rotation

DANGER!
Hazard of electrical shock! Wait three minutes after disconnecting incoming power
before servicing drive. Capacitors retain charge after power is removed.
STOP!
• DO NOT connect incoming AC power to output terminals U, V, and W or terminals
B+, B-! Severe damage to the drive will result. Do not continuously cycle input power
to the drive more than once every two minutes. Damage to the drive will result.
• Severe damage to the drive can result if it is operated after a long period of
storage or inactivity without reforming the DC bus capacitors!
Refer to Section 3.1, Installation After a Long Period of Storage
Before attempting to operate the drive, motor, and driven equipment, be sure all procedures pertaining
to installation and wiring have been properly followed.
Disconnect the driven load from the motor. Verify that the drive input terminals (L1 and L2/N, or L1,
L2, and L3) are wired to the proper input voltage per the nameplate rating of the drive.
Energize the incoming power line. The LED display will flash a three digit number (320 in the example
below) that identifies the parameter version contained in the drive. The display should then read "- - -",
which indicates that the drive is in a STOP condition. This is shown below:
Apply input power
Display flashes parameter
version (300-399)
Display then reads "- - -"
Follow this 4-step procedure to check the motor rotation. This procedure assumes that the drive has
been powered up for the first time, and that none of the parameters have been changed.
Use the q button to decrease the speed setpoint to 00.0 Hz. The left decimal point will illuminate
1.
as the speed setpoint is decreased. If the q button is held down, the speed setpoint will decrease
by tenths of Hz until the next whole Hz is reached, and then it will decrease by one Hz increments.
Otherwise, each push of the q button will decrease the speed setpoint by a tenth of a Hz.
Once 00.0 Hz is reached, the display will toggle between "00.0" and "- - -", which indicates that
the drive is in a STOP condition with a speed setpoint of 00.0 Hz.
2.
Give the drive a START command. This can be done using one of several wiring methods described
in Section 3.6, SCL/SCM Control Wiring Diagrams. Once the START command is issued, the display
will read "00.0", indicating that the drive is in a RUN condition with a speed setpoint of 00.0 Hz.
Use the p button to increase the speed setpoint until the motor starts to rotate. The left decimal
3.
point will light as the speed setpoint is increased. If the p button is held down, the speed setpoint
will increase by tenths of Hz until the next whole Hz is reached, and then it will increase by one
Hz increments. Otherwise, each push of the button will increase the speed setpoint by a tenth
of a Hz.
Lenze 13466147 EDBSM01 v19 EN
Commissioning
4
25