Start; Technical Data - Beckhoff EL1512 Documentation

Up/down counter 24 vdc
Table of Contents

Advertisement

Product overview
2.2.2

Technical data

Technical data
Connection technology
Specification
Number of inputs
Rated voltage
Signal voltage "0"
Signal voltage "1"
Input current
Counting frequency
Counter depth
Current consumption power contacts
Current consumption via E-bus
Electrical isolation
Supports NoCoeStorage [} 22] function
Configuration
Special features
Weight
Permissible ambient temperature range
during operation
Permissible ambient temperature range
during storage
Permissible relative humidity
Dimensions (W x H x D)
Mounting [} 28]
Vibration/shock resistance
EMC immunity/emission
Protection class
Installation position
Approval
2.3

Start

For commissioning:
• mount the EL15xx as described in the chapter Mounting and wiring [} 28]
• configure the EL15xx in TwinCAT as described in the chapter Commissioning [} 109].
16
EL1512
1 x up/down counter, 2 x up or down counter
EN 61131-2, type 1, "0":< 5 V
5 mA typ.
1 or 2
24 V
(-15%/+20%)
DC
-3 V ... 5 V (EN 61131-2, type 1)
15 V ... 30 V (EN 61131-2, type 1)
typically 5 mA (EN 61131-2, type 1)
max. 1 kHz
32 bit
typ. 14 mA + load
typ. 130 mA
500 V (E-bus/field voltage)
yes
via TwinCAT System Manager
Set counters
approx. 50 g
-25°C ... +60°C (extended temperature range)
-40°C ... +85°C
95%, no condensation
approx. 15 mm x 100 mm x 70 mm
on 35 mm mounting rail conforms to EN
60715
conforms to EN 60068-2-6 / EN 60068-2-27,
see also installation instructions [} 31] for
enhanced mechanical load capacity
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE
ATEX [} 38]
cULus [} 39]
Version: 3.5
, "1":> 15 V
,
DC
DC
EL1502, EL1512

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

El1502

Table of Contents