2.1.2
Technical data
Technical data
Number of counters
Rated voltage
Signal voltage "0"
Signal voltage "1"
Counting frequency
Counter depth
Input current
Output current (per channel)
Distributed Clocks (DC)
Current consumption power
contacts
Current consumption via E-bus
Electrical isolation
Supports NoCoeStorage [} 22]
function
Configuration
Weight
Permissible ambient temperature
range during operation
Permissible ambient temperature
range during storage
Permissible relative humidity
Dimensions (W x H x D)
Mounting [} 28]
Vibration/shock resistance
EMC immunity/emission
Protection class
Installation position
Approval
14
EL1502
1 or 2
24 V
(-15%/+20%)
DC
-3 V ... 5 V (EN 61131-2, type 1)
15 V ... 30 V (EN 61131-2, type 1)
100 kHz
32 bit
typ. 5 mA (EN 61131-2, type 1)
max. 0.5 A (short-circuit-proof)
yes (from FW 02)
typ. 14 mA + load
typ. 130 mA
500 V (E-bus/field voltage)
yes
via TwinCAT System Manager
approx. 50 g
-25°C ... +60°C (extended temperature range)
-40°C ... +85°C
95%, no condensation
approx. 15 mm x 100 mm x 70 mm
on 35 mm mounting rail conforms to EN 60715
conforms to EN 60068-2-6 / EN 60068-2-27,
see also installation instructions [} 31] for
enhanced mechanical load capacity
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE
ATEX [} 38]
cULus [} 39]
Version: 3.5
EL1502, EL1512