To enable/disable Zone 2 Remote Temperature:
1) Press MENU key to go to the Main Menu
screen.
2) Use UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to IO Config;
press ENTER key.
4) Press UP or DOWN keys to scroll to Z2 Remote
Temp C9.
5) Press ENTER key to scroll to Enable (see
Figure 38).
6) Press UP or DOWN key to change value to ON
to enable sensor (or change value to OFF to
disable sensor).
FIGURE 38
Enable/Disable Zone 2 Remote Temperature Sensor
To enable/disable Zone 3 Remote Temperature:
1) Press MENU key to go to the Main Menu
screen.
2) Use UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to IO Config;
press ENTER key.
4) Press UP or DOWN keys to scroll to Z3 Remote
Temp C10.
5) Press ENTER key to scroll to Enable (see
Figure 39).
6) Press UP or DOWN key to change value to ON
to enable sensor (or change value to OFF to
disable sensor).
Manual 2100-676B
Page
42 of 88
FIGURE 39
Enable/Disable Zone 3 Remote Temperature Sensor
6. Enter Total Number of Units
1) Press MENU key to go to the Main Menu
screen.
2) Press UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to Sys Config;
press ENTER key.
4) Press UP or DOWN keys to scroll to General;
press enter key.
5) Press ENTER key to scroll to Total Units (see
Figure 40).
6) Press UP or DOWN keys to adjust value to
correct number of units.
7) Press ENTER key to save value.
8) Press the ESCAPE key several times to return
to Main Menu screen.
FIGURE 40
Total Units Displayed
7. Verify Units Are Online
Once a unit is uniquely addressed, communication
can be verified at the LC controller.
With the correct number of units set at the LC
controller, each unit can be remotely viewed from
the controller information screen.
To view these screens:
1) Press ESCAPE key to view the Status screen.
(May need to be pressed more than once.)