Enable/Disable Zone 1 Indoor Humidity Sensor; Figure; Enable/Disable Zone 2 Indoor Humidity Sensor; Enable/Disable Zone 3 Indoor Humidity Sensor - Bard MULTI-TEC W24AAPA Installation Instructions Manual

Wr series wall-mount air conditioner lc6000-100 controller free cooling unit system
Table of Contents

Advertisement

5. Configure Sensors
The system will need to be configured for the
number of temperature and humidity sensors
installed. The system is shipped with one
combination temperature and humidity sensor.
Additional combination sensors may be purchased
or alternatively, temperature-only sensors may be
purchased instead. The LC is capable of utilizing
four temperature sensors and three humidity
sensors. The system will need to be configured for
the various configurations.
If necessary, the sensors could be calibrated at this
time too. For information on calibrating the sensors
(adjusting the offset), see page 87.
To enable/disable Zone 1 Indoor Humidity:
1) Press MENU key to go to the Main Menu
screen.
2) Press UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to IO Config;
press ENTER key.
4) Press UP or DOWN keys to scroll to Z1 Indoor
Hum C4.
5) Press ENTER key to scroll to Enable (see

Figure 44).

6) Press UP or DOWN key to change value to ON
to enable sensor (or change value to OFF to
disable sensor).
FIGURE 44

Enable/Disable Zone 1 Indoor Humidity Sensor

To enable/disable Zone 2 Indoor Humidity:
1) Press MENU key to go to the Main Menu
screen.
2) Press UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to IO Config;
press ENTER key.
4) Press UP or DOWN keys to scroll to Z2 Indoor
Hum C5.

Manual 2100-676B

Page
84 of 88
5) Press ENTER key to scroll to Enable (see
Figure 45).
6) Press UP or DOWN key to change value to ON
to enable sensor (or change value to OFF to
disable sensor).
FIGURE 45

Enable/Disable Zone 2 Indoor Humidity Sensor

To enable/disable Zone 3 Indoor Humidity:
1) Press MENU key to go to the Main Menu
screen.
2) Press UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to IO Config;
press ENTER key.
4) Press UP or DOWN keys to scroll to Z3 Indoor
Hum C6.
5) Press ENTER key to scroll to Enable (see
Figure 46).
6) Press UP or DOWN key to change value to ON
to enable sensor (or change value to OFF to
disable sensor).
FIGURE 46

Enable/Disable Zone 3 Indoor Humidity Sensor

To enable/disable Zone 1 Indoor Temperature:
1) Press MENU key to go to the Main Menu
screen.
2) Use UP or DOWN keys and ENTER key to
enter USER password 2000.

Advertisement