Minimum Clearance

Counter flow wall-mount air conditioner models have
a removable lower front service panel that allows
access to the control panel, blower, compressor, circuit
breakers and heat strip. There is a hinged access panel
on both sides for filter change and evaporator coil
service.
The upper side panel is removable to allow access
to condenser fan, condenser coil and filter drier. The
design allows for installations to place units within
close proximity without complicating maintenance and
repair.
To maintain full serviceability, side-by-side installations
require 15" of clearance between units.
The condenser discharge air exits through the top
of the unit. Although this reduces the potential for
recirculation, it is still critical to system performance
that any obstruction, shrubbery or structure adhere to
minimum clearances listed (see Table 1).
For overhangs not exceeding 12" from exterior wall,
minimum allowable clearance from top of unit
to bottom of overhang should be no less than 5".
For overhangs greater than 12" from exterior wall,
minimum allowable clearance from top of unit to
bottom of overhang should be no less than 10".
Clearance Required for Service Access and Adequate Condenser Airflow
Discharge (Top)
Model
Side(s)
Overhang 12" or less
WR36
15"
WR58
15"

Manual 2100-676B

Page
54 of 88
TABLE 1
Discharge (Top)
Overhang
Exceeding 12"
5"
10"
5"
10"
TABLE 2
Minimum Clearances Required to Combustible Materials
Model
Supply Air Flange
WR36
1/4"
WR58
1/4"

Clearance to Combustibles

The unit itself is suitable for 0" clearance, but the
supply air flange requires a minimum of 1/4" clearance
to combustible material. However, it is generally
recommended that a 1" clearance is used for ease of
installation and maintaining the required clearance
to combustible material. See Figure 8 on page 59 for
details on opening sizes.
WARNING
!
Fire hazard.
Maintain minimum 1/4" clearance between the
supply flange and combustible materials.
Failure to do so could result in fire causing
damage, injury or death.
Intake (Base)
Front of Unit
15" from
Snowline
15" from
Snowline
Cabinet
0"
0"
Shelter
Equipment from
Supply Grille
36"
24"
36"
24"