WARNING
!
Electrical shock hazard.
Have a properly trained individual perform
these tasks.
Failure to do so could result in electric shock
or death.
MAIN POWER WIRING
Refer to the unit rating plate or Table 1.1 (page 18)
or Table 1.2 (page 19) for wire sizing information and
maximum fuse or circuit breaker size. Each outdoor
unit is marked with a "Minimum Circuit Ampacity".
The field wiring used must be sized to carry that
amount of current. Depending on the installed KW of
electric heat, there may be two field power circuits
required. If this is the case, the unit rating plate will
so indicate. All models are suitable only for connection
with copper wire. Each unit and/or wiring diagram
will be marked "Use Copper Conductors Only". These
instructions must be adhered to. Refer to the National
Electrical Code (NEC) for complete current carrying
capacity data on the various insulation grades of wiring
material. All wiring must conform to NEC and all local
codes.
The unit rating plate and Tables 1.1 and 1.2 list fuse
and wire sizes (75°C copper) for all models including
the most commonly used heater sizes. Also shown are
the number of field power circuits required for the
various models with heaters.
The unit rating plate lists a maximum circuit breaker or
fuse that is to be used with the equipment. The correct
size must be used for proper circuit protection and also
to assure that there will be no nuisance tripping due to
the momentary high starting current of the compressor
motor.
Route all field wires to the right of the wire shield as
shown in the circuit routing label found in Figure 1.9
(and also on the wall-mount units).
See Figure 1.10 to reference VAC landing points.
The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect. To
convert for the locking capability, bend the tab located
in the bottom left-hand corner of the disconnect
opening under the disconnect access panel straight
out. This tab will now line up with the slot in the door.
When shut, a padlock may be placed through the hole
in the tab preventing entry.

WALL-MOUNT UNIT SUPPLY WIRING

VAC Supply Wiring Landing Points
Factory
Wiring
A
3/17/2014 ADDED FRENCH VERSION
REV.
DATE
NOTE: Right-hand access model wiring landing points
are shown here; left-hand access models will
mirror this image.
LOW VOLTAGE WIRING
230/208V 1 phase and 3 phase equipment use dual
primary voltage transformers. All equipment leaves the
factory wired on 240V tap. It is very important that
the correct voltage tap is used. For 208V operation,
reconnect from 240V to 208V tap. The acceptable
operating voltage range for the 240 and 208V taps are:
240V Tap (253 – 216) and 208 Tap (220 – 197).
NOTE: The voltage should be measured at the field
power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition.
For low voltage wiring, an 18 guage copper, color-coded
cable is recommended.
FIGURE 1.9

Circuit Routing Label

NOTICE / AVIS
ROUTE ALL HIGH VOLTAGE FIELD
WIRES TO THE RIGHT OF THE WIRE
SHIELD AS SHOWN
ACHEMINER LES FILS HAUTE
TENSION SUR LA DROITE VERS LA
PROTECTION, COMME INDIQUÉ
CIRCUIT BREAKER
/DISJONCTEUR
WIRE SHIELD /
5.000
PROTECTION
7961-393
FIGURE 1.10
2.500
MATERIAL : OUTDOOR VINYL
BACKGROUND COLOR : WHITE / SAFETY BLUE
PRINTING COLOR : BLACK 1/8" LETTERING
SIZE : 2.500 X 5.000
FORMAT : ROLL
11182
DESCRIPTION
ECN NO DRN CHK APR
Manual 2100-665A
Page
WHITE 3/16" LETTERING
Field
Wiring
MAT'L
WIRING ROUTING LABEL
PART
NAME
PART
7961-393
DWG.
7961-393
A
A
NO.
NO.
DATE
3/17/2014
3/17/2014
1:4
DAY
SCALE
DRAWN BY
Bard Mfg. Co.
SD
RP
RP
Bryan, Ohio
BD SD RP
CHECKED
APPROVED
DISTRIBUTION
1 2 3 4 5
17 of 51

Advertisement

Table of Contents
loading

Table of Contents