Communication Wiring: Termination at Additional Wall-Mount Units
Unit 2 Terminal Block
1
2
3
4
5
6
7
8
9 10
+
1.
Route the cable from the first wall-mount unit to the
terminal block of the second wall-mount unit. If this is
the last unit to be connected, make a small service loop
and attach EMI filter as shown.
2.
Connect the wires matching the terminal
designations (+/-) of the controller terminals.
Cap the loose drain with a wire nut or
electrical tape.
3.
Continue daisy chaining units by connecting
"+" to "+", "-" to "-" and wire nutting drain
together until last unit which is capped with
a wire nut. Attach EMI filter as shown above
at last unit. Up to 14 wall-mount units can
be connected and controlled by one LC6000
controller.

Manual 2100-676B

Page
76 of 88
FIGURE 29
11
12
13
14
15
16 17
From Wall-Mount
Unit 1
Wall-Mount Unit 2
Unit 2 Terminal Block
1
2
3
4
5
6
7
8
9 10
+
11
12
13
14
15
16 17
From Wall-Mount
Unit 1