Figure 53 Adjusting Sensor Offset Value; Table; Lc6000/Tec-Eye Passwords (Default); Manual 2100-676B - Bard MULTI-TEC W24AAPA Installation Instructions Manual

Wr series wall-mount air conditioner lc6000-100 controller free cooling unit system
Table of Contents

Advertisement

Menu Screens and Password Levels
WR Series Unit
System Config: A1-A10 User (2000)
Adv. System Config: B1-B4 Technician (1313)
I/O Config: C1-C18 Technician (1313)
On/Off: User (2000)
Alarm Logs: User (2000)
Settings
Date/Time: Technician (1313)
Language: User (2000)
Network Config: Technician (1313)
Serial Ports: Technician (1313)
Initialization
Clear Logs: User (2000)
System Default: Engineer (9254)
Restart: User (2000)
Parameter Config: Engineer (9254)
Alarm Export: User (2000)
Logout: Used to log out of the current password
level. Entering back into the menu requires
password.
LC1000 Controller
System Config
General: User (2000)
Zone 1: User (2000)
Zone 2: User (2000)
Zone 3: User (2000)
Adv. System Config: B1-B13 Technician (1313)
I/O Configuration: C1-C10 Technician (1313)
On/Off: User (2000)
Alarm Log: User (2000)
Settings
Date/Time: Technician (1313)
Language: User (2000)
Network Config: Technician (1313)
Initialization
Clear Logs: User (2000)
System Default: Engineer (9254)
Restart: User (2000)
Parameter Config: Engineer (9254)
Alarm Export: User (2000)
Logout: Used to log out of the current password
level. Entering back into the menu requires
password.

TABLE 5

LC6000/TEC-EYE Passwords (Defaults)
User
Technician
Engineer
Use UP or DOWN keys and ENTER key to enter password
ADDITIONAL INFORMATION
Setpoints
The LC6000 setpoints will determine the cooling and
heating setpoints when communicating with the wall-
mount units. The unit cooling and heating setpoints
will determine the cooling and heating setpoints when
in stand alone mode.
If at any time the unit(s) loses communication with the
LC6000 controller, the unit(s) will go into stand alone
mode.
Calibrating Sensors
1. Press MENU key on LC controller interface to go to
2. Use UP or DOWN keys and ENTER key to enter
3. Press UP or DOWN keys to scroll to I/O Config;
4. Press UP or DOWN keys to scroll to sensor to be
5. Press ENTER key to scroll to Offset (see Figure
6. Press UP or DOWN keys to add or subtract to the
7. Press ENTER key to save.
2000
1313
9254
the Main Menu screen.
USER password 2000.
press ENTER key.
adjusted.
53).
sensor offset value.
FIGURE 53
Adjusting Sensor Offset Value

Manual 2100-676B

Page
87 of 88

Advertisement

Table of Contents
loading

Table of Contents