For proper operation, the remote indoor temperature/humidity sensor must be configured properly with the controller.
An additional remote indoor temperature-only sensor can be purchased and installed in Zone 1. Also, temperature
and humidity sensors can also be purchased and installed in Zones 2 and 3 (one per zone). For information on
remote indoor sensor configuration, see page 26. For each additional sensor installed, be sure to enable the sensor
in the controller menus (see Configure Sensors beginning on page 40).
Additional Remote Temperature and Temperature/Humidity Sensor Installation
One additional temperature sensor can be added to Zone 1 and additional temperature/humidity sensors may be
added to Zones 2 and 3 (one per zone). Be sure the sensors are connected to the proper terminals on the terminal
block and sensor as listed below.
1
2
3
4
5
6
Zone 1:
Optional Remote
Temperature Sensor
Terminals 20 & 21*
Zone 2:
Optional Remote
Temperature/Humidity Sensor
Terminals 26, 27, 14, 15 & 23
Zone 3:
Optional Remote
Temperature/Humidity Sensor
Terminals 28, 29, 16, 17 & 24
Zones 2 and 3 can also use temperature-only sensors in place of the temperature/humidity sensors. Zone 2 will connect
to TB# 26 and 27. Zone 3 will connect to TB# 28 and 29. The wire connections for the temperature-only sensors are not
polarity sensitive.

FIGURE 15

7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Wire
TB#
Mark
20
B7
Indoor Remote Sensor (Zone 1 – optional)
21
GND
Ground
* The two wire connections for the optional remote temperature sensor
are not polarity sensitive.
Wire
TB#
Sensor
Mark
26
B8
NTC OUT Indoor Remote Sensor (Zone 2)
27
GND
NTC OUT Ground
14
B3
OUT H
15
GND
M (GO)
23
+VDC
Wire
TB#
Sensor
Mark
28
B9
NTC OUT Indoor Remote Sensor (Zone 3)
29
GND
NTC OUT Ground
16
B4
OUT H
17
GND
M (GO)
24
+VDC
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
Description
Remote Indoor Humidity Sensor: 0-1 VDC (Zone 2)
Ground
+ (G)
Power for B3
Remote Indoor Humidity Sensor: 0-1 VDC (Zone 3)
Ground
+ (G)
Power for B4
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
Description
Description
Manual 2100-676B
Page
57
58
59
60
27 of 88