Manual 2100-676B - Bard MULTI-TEC W24AAPA Installation Instructions Manual

Wr series wall-mount air conditioner lc6000-100 controller free cooling unit system
Table of Contents

Advertisement

Wire
TB#
Mark
1
-
115 VAC Input
2
-
208 VAC Input
3
-
240 VAC Input
4
-
Power Input Common
5
-
Power Input Ground
6
DI1
Smoke Detector Input
7
GND
Smoke Detector Common
8
DI2
Hydrogen Detector Input
9
GND
Hydrogen Detector Common
10
DI3
Generator Run Input
11
GND
Generator Run Common
12
B2
Indoor Remote Humidity Sensor (Zone 1)
13
GND
Ground
14
B3
Indoor Remote Humidity Sensor (Zone 2)
15
GND
Ground
16
B4
Indoor Remote Humidity Sensor (Zone 3)
17
GND
Ground
18
B6
Indoor Temperature Sensor (Zone 1)
19
GND
Ground
Indoor Remote Temperature Sensor
20
B7
(Zone 1)
21
GND
Ground
22
VDC+
Power for B2 (Z1 Humidity)
23
VDC+
Power for B3 (Z2 Humidity)
24
VDC+
Power for B4 (Z3 Humidity)
25
VDC+
Power for B10 (Pressure)
Indoor Remote Temperature Sensor
26
B8
(Zone 2)
27
GND
Ground
Indoor Remote Temperature Sensor
28
B9
(Zone 3)
29
GND
Ground

Manual 2100-676B

Page
78 of 88
TABLE 4
LC6000-100 Terminal Block Index
Description
Wire
TB#
Mark
30
B10
Indoor Space Pressure
31
GND
Ground
32
NO1
Humidifier 1
33
C1
Common
34
NO2
Humidifier 2
35
C1
Common
36
NO3
Humidifier 3
37
C1
Common
38
NO4
Smoke Alarm
39
C2
Common
40
NO5
Hydrogen Alarm
41
C2
Common
42
NO6
Generator Alarm
43
C2
Common
44
NO7
Indoor Humidity Alarm
45
C7
Common
46
NO8
High Indoor Temperature Alarm
47
C8
Common
48
NO9
Low Indoor Temperature Alarm
49
C8
Common
50
NO10
Zone 1 Unit Alarm
51
C8
Common
52
NO11
Zone 2 Unit Alarm
53
C8
Common
54
NO12
Zone 3 Unit Alarm
55
C8
Common
56
FB1R-
RS485 RX- / TX- (Fieldbus 1)
57
FB1R+ RS485 RX+ / TX- (Fieldbus 1)
58
FB2R-
RS485 RX- / TX- (Fieldbus 2)
59
FB2R+ RS485 RX+ / TX- (Fieldbus 2)
60
-
Ground
Description