Dect Overview - Aidcall Touchsafe Pro IP-DECT 400 Single-Cell Installation Manual

Wireless nursecall system
Table of Contents

Advertisement

5. DECT OVERVIEW 
 
The maximum theoretical range for any DECT system is 500 metres under ideal conditions, in practice the 
range will rarely exceed 300 metres due to reflections from nearby buildings, trees, water, etc.  
 
Obstructions inside buildings such as walls and floors will reduce the range, some construction materials 
such as foil backed plasterboard, reinforced concrete or stone walls will reduce range further.  
 
Environmental conditions such as high levels of transmission at nearby frequencies or emissions from other 
electrical equipment may also reduce range.  
 
Clear line‐of‐sight will give maximum radio coverage, it is impossible to state a specific indoor range in 
advance of a site survey; however, as a guide you can usually achieve 50 metres radius from the 
Server/Base Station or Repeater. 
 
Locating the Server/Base Station as high and free from immediate obstruction as possible will help to 
maximise its range. Even if the Server/Base Station is placed in the optimum position it may not always 
achieve coverage in the most remote corners, if this is the case then additional Repeaters will be required. 
 
Repeaters are generally placed in a star configuration around the Server/Base station; however, it is 
possible to extend the coverage in one direction with up to 3 repeater jumps. A site survey will be required 
to establish the best DECT system and Base/Repeater configuration required.  
 
The Server, Base Stations and Repeaters should always be located at least 5 metres away from the 
Nursecall Panels, RFE's or any other electrical equipment to avoid the risk of interference. 
 
All DECT products must be sited in a dry secure area; they are NOT suitable for outdoor locations.   
 
 
 
AVOID LOCATING DECT PRODUCTS...
 
 
 
 
WITHIN 5 METRES OF 
DIRECTLY ABOVE A 
IN DIRECT SUNLIGHT
NEAR TO SPLASHING 
OTHER ELECTRONIC 
HEATER 
WATER 
EQUIPMENT 
 
 
IMPORTANT NOTE:
 
Care must be taken during installation and commissioning of any DECT system to ensure full radio 
coverage and correct Radio Part Numbering of Base Stations and Repeaters. Failure to follow the 
Manufacturer's installation and programming instructions may result in blind spots or calls dropping‐out 
when moving between radio cells. Always perform several test calls in all extremes of the building with all 
DECT handsets in use, i.e. simultaneous phone‐phone calls.      
 
 
 
 
 
 
 
 
 
 
 
 
 
ENTS
 
Doc No. FM5640 issue 3 Page 6   
 

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Touchsafe Pro IP-DECT 400 Single-Cell and is the answer not in the manual?

Table of Contents