Table 13: Pid Tuning Parameters - Honeywell ST700 User Manual

Foundation fieldbus pressure transmitter
Hide thumbs Also See for ST700:
Table of Contents

Advertisement

The values given for these tuning parameters are valid under the following conditions:
The values assume that the minimum configurable PID function block execution period
(T
) is 0.125 seconds.
s
Algorithm typesetting (A, B, or C) has no effect on the validation of these tuning
parameters.
The PID function block rejects all values outside the following ranges:
Parameter
Initial
Value
PV_FTIME
0
GAIN
0
GAIN_NLIN
0
RATE
0
(sec.)
RESET
+INF
(sec.)
OUT_LAG
Ideal PID
N/A
Robust PID
0
BAL_TIME
0
Page 56
FOUNDATION Fieldbus ST 700 Pressure Transmitter User's Guide

Table 13: PID Tuning parameters

Minimum
Maximum
Value
Value
0
200
.004
250
.004
250
32 • T
7500
s
2 • T
7500
s
N/A
N/A
2 • T
7500
s
N/A
N/A
Comment
Units: seconds.
The value of ZERO is permitted to turn
off rate action.
The value of +INF is permitted to turn
off reset action. (Some versions of NI
configurator program cannot set +/-
INF).
Fixed for Ideal PID form - not
configurable.
Zero permitted which implies no output
lag.
Not used in Honeywell Implementation.
Revision 2.0