Incorrect Or Non-Compatible Tools - Honeywell ST700 User Manual

Foundation fieldbus pressure transmitter
Hide thumbs Also See for ST700:
Table of Contents

Advertisement

Incorrect or non-compatible tools

If non-compatible versions of fieldbus software tools are used, such as Standard Dictionary
or Device Description (DD) files, or if you are using the incorrect revision level of device
firmware, then device objects or some block objects may not be visible or identified by
name. See the following table for the possible causes and recommended actions.
Device and/or block objects not identified (Unknown).
Or
Parameters are not visible or identified by name.
Or
Honeywell-defined parameters are not visible.
Possible cause
Incorrect Standard
Dictionary, Device
Description (DD) or
Symbols on host
computer.
Incorrect pathnames to
descriptions on host
computer.
Incorrect version of
device firmware
Page 96
FOUNDATION Fieldbus ST 700 Pressure Transmitter User's Guide
Symptoms
Things to check
Verify that the Standard
Dictionary, the DD or symbols
files are correct for the device.
Check that the pathnames to
locations of the Standard
Dictionary, and DD files on the
host computer are correct.
Read the following Resource
block parameters:
DEV_REV (contains the
revision level of the
resource block).
DD_REV (contains the
revision level of the
resource block).
Recommended action
Install the compatible version of Standard
Dictionary and DD for the device on the
host computer.
Make sure that the pathnames of the
Standard Dictionary and DD are in the
correct location for the fieldbus software
application.
Perform a code download of the correct
device firmware. See section 5.2.
Revision 2.0