Parameter
FD_CHECK_PRI
FD_CHECK_MAP
FD_CHECK_MASK
FD_CHECK_ACTIVE
FD_CHECK_ALM
FD_SIMULATE
HARDWARE_REV
SOFTWARE_REV
MODEL_KEY
MOD_PART_1
MOD_PART_2
MOD_PART_3
MOD_PART_4
HW_SIMULATE_JUM
PER_STATE
INSTALL_DATE
MAINTENANCE_MO
DE
Attributes
Supported Modes
Alarm Types
Page 24
FOUNDATION Fieldbus ST 700 Pressure Transmitter User's Guide
Designates the alarming priority of the CHECK_ALM. The valid range is 0-
15.
Mapped CHECK_ALM alarm conditions. Corresponds bit for bit to the
CHECK_ACTIVE. A bit on means that the corresponding alarm condition is
Mapped and is detected. A bit off means the corresponding alarm condition
is disabled and is not detected.
Mask of CHECK_ALM. It corresponds to the bit of bit to CHECK_ACTIVE. A
bit on means that the condition is masked out from alarming.
Enumerated list of check conditions within a device.
Alarm indicating check alarms. These conditions do not have a direct impact
on the process or device integrity.
When simulation is enabled, the Field Diagnostics conditions are taken from
Diagnostic Simulate Value, or else the conditions are taken from Diagnostic
Value.
The hardware revision number of the communications module.
The software revision number of the communications module.
The key number of ST 700 pressure transmitter (Example: STD 810).
First part of the Material of Construction Information.
Second part of the Material of Construction Information.
Third part of the Material of Construction Information.
Fourth part of the Material of Construction Information.
State of Hardware Simulation Jumper (Enabled / Disabled).
The date and time when the device is installed in the field. The date and
time is directly acquired from the FF Host.
It indicates whether device is ready for maintenance.'Chk with Oper'- Check
with operator to determine availability. 'Avail for Maint'- The device is
available for maintenance.
The block supports the following modes:
AUTO (Automatic)
IMAN (Manual)
OOS (Out of Service).
The block supports standard block alarms (see section 3.2), and
added to it, a discrete alarm for write lock.
Description
Revision 2.0