Disable the SIMULATE parameter.
(Set transmitter for normal operation.)
Enable the SIMULATE parameter.
(For testing or debugging purposes.)

Enabling simulation mode

The SIMULATE parameter is enabled by setting the hardware simulation jumper to the
"ON" position.
In addition, the AI block SIMULATE parameter must be set to the following values:
SIMULATE.STATUS = Good::[alarm status]:constant (suggested setting)
SIMULATE.SIMULATE_VALUE = (supplied by user) Used as the input to the AI
block.
SIMULATE.ENABLE_DISABLE = Active Enabled.

Simulation mode truth table

Table 36 shows the states of the simulation jumper and SIMULATE parameter shows how
to activate the simulation mode.
When the Simulation
Jumper on Transducer
board is set to:
"OFF" Position
"ON" Position

Setting Al block mode

To connect the AI block input to the output, the AI block must be in AUTO mode.
Revision 2.0
FOUNDATION Fieldbus ST 700 Pressure Transmitter User's Guide

Table 35: Setting the Simulation Jumper

To
"OFF" position on the Transducer board.

Table 36: Simulation Mode Truth Table

and the SIMULATE Enable_Disable is set to:
(Disabled)
Simulation Disabled
Simulation Disabled
Set the Jumper to:
"ON" position on the Transducer board.
(Active)
Simulation Disabled
Simulation Active
Page 117