Specifications
7.10 Fuse and Circuit Breaker Specifications
Overcurrent protection
Provide overload protection to avoid overheating of the cables in the installation. Always carry out overcurrent protection
according to local and national regulations. Design fuses for protection in a circuit capable of supplying a maximum of
100000 A
(symmetrical), 480 V maximum. See Table 7.15 and Table 7.16 for breaking capacity for Danfoss CTI25M circuit
rms
breaker at 480 V maximum.
UL/non-UL compliance
To ensure compliance with UL 508C or IEC 61800-5-1, use the circuit breakers or fuses listed in Table 7.15, Table 7.16, and
Table 7.17.
NOTICE
EQUIPMENT DAMAGE
If there is a malfunction, failure to follow the protection recommendation can result in damage to the frequency
converter.
Enclosure
7
7
size
MH1
MH2
MH3
Table 7.15 Circuit Breakers, UL
Enclosure
size
MH1
MH2
MH3
Table 7.16 Circuit Breakers, Non-UL
1) Trip level maximum set to 32 A.
52
VLT® DriveMotor FCP 106/FCM 106
1)
Power
[kW (hp)]
3x380–480 V
Recommended UL
0.55 (0.75)
CTI25M - 47B3146
0.75 (1.0)
CTI25M - 47B3147
1.1 (1.5)
CTI25M - 47B3147
1.5 (2.0)
CTI25M - 47B3148
2.2 (3.0)
CTI25M - 47B3149
3.0 (4.0)
CTI25M - 47B3149
4.0 (5.0)
CTI25M - 47B3150
5.5 (7.5)
CTI25M - 47B3150
7.5 (10)
CTI25M - 47B3151
1)
Power
[kW (hp)]
Recommended
3x380–480 V
0.55 (0.75)
CTI25M - 47B3146
0.75 (1.0)
CTI25M - 47B3147
1.1 (1.5)
CTI25M - 47B3147
1.5 (2.0)
CTI25M - 47B3148
2.2 (3.0)
CTI25M - 47B3149
3.0 (4.0)
CTI25M - 47B3149
4.0 (5.0)
CTI25M - 47B3150
5.5 (7.5)
CTI25M - 47B3150
7.5 (10)
CTI25M - 47B3151
Danfoss A/S © 11/2015 All rights reserved.
Circuit breaker
Breaking
capacity
100000
100000
100000
100000
50000
50000
6000
6000
6000
Circuit breaker
Breaking
non-UL
capacity
100000
100000
100000
100000
100000
100000
50000
50000
15000
Maximum UL
CTI25M - 047B3149
CTI25M - 047B3149
CTI25M - 047B3150
CTI25M - 047B3150
CTI25M - 047B3151
CTI25M - 047B3151
CTI25M - 047B3151
CTI25M - 047B3151
CTI25M - 047B3151
Maximum non-UL
CTI25M - 47B3149
CTI25M - 47B3149
CTI25M - 47B3150
CTI25M - 47B3150
CTI25M - 047B3151
CTI25M - 047B3151
1)
CTI25M - 047B3102
1)
CTI25M - 047B3102
CTI25M - 047B3102
1)
Breaking
capacity
50000
50000
6000
6000
6000
6000
6000
6000
6000
Breaking
capacity
100000
100000
50000
50000
15000
15000
15000
15000
15000
MG03L302