Thermistor Input From Motor; Ac Mains Connection; Mg03L302 - Danfoss VLT DriveMotor FCP 106 Operating Instructions Manual

Hide thumbs Also See for VLT DriveMotor FCP 106:
Table of Contents

Advertisement

Electrical Installation

4.6.2 Thermistor Input from Motor

Connect the motor thermistor to the terminals located in
the motor connector, as shown in chapter 4.6.1 Connect FCP
106 to Motor.
Set parameter 1-90 Motor Thermal Protection according to
guidelines in chapter 5.4.5 Thermistor Set-up. For more
4
4
detailed information, refer to the VLT
and FCM 106 Programming Guide.
NOTICE
The thermistor is not galvanically isolated. Interchanging
the thermistor wires with the motor wires may
permanently damage the frequency converter.

4.7 AC Mains Connection

4.7.1 Connecting to Mains
The frequency converter is designed to operate all
standard 3-phased asynchronous motors and PM motors.
For maximum cross-section on wires, see
chapter 7.2.1 Mains Supply 3x380–480 V AC Normal and High
Overload.
FCP 106 wall mount
To comply with EMC emissions requirements:
-
-
See also chapter 4.3 EMC-compliant Installation.
Procedure for connection of mains power
1.
Observe safety precautions, see chapter 2.2 Safety
Precautions.
2.
Loosen front cover screws.
3.
Remove the front cover, see Illustration 4.7.
4.
Mount cable glands fulfilling the requirements for
the needed enclosure integrity.
5.
Connect the ground wires to the ground
terminals via the cable glands, see Illustration 4.8.
6.
Connect the mains cable to terminals L1, L2, and
L3, and tighten the screws. See Illustration 4.8.
7.
Reassemble cover and tighten screws.
8.
For tightening torques, see chapter 7.8 Connection
Tightening Torques.
24
VLT® DriveMotor FCP 106/FCM 106
®
DriveMotor FCP 106
Use screened motor cable, maximum
length 0.5 m (1.64 ft).
Connect this cable to the metal housing
of both the frequency converter and the
motor.
Danfoss A/S © 11/2015 All rights reserved.
1
LCP extension cable entry
2, 3
Entries for other cables: Control, RS485, and relay
cables
4
Mains cable entry
Illustration 4.6 Location of Cable Entries, MH1–MH3
Illustration 4.7 Remove Front Cover
4
3
2
1

MG03L302

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt drivemotor fcm 106

Table of Contents