Technical Data - ABB DCS880 series Hardware Manual

20 ... 5200 a
Hide thumbs Also See for DCS880 series:
Table of Contents

Advertisement

Technical data

Auxiliary incoming power XAUX (X99)
Auxiliary
voltage
Tolerance
Frequency
Power consump-
tion
Power loss
Inrush current
Recommended
fusing
Mains buffering
Powerfail
Input circuit XAUX (X99)
Features a hardware filter
and a voltage limitation.
3ADW000462R0101 DCS880 Hardware Manual e a
115 V
AC
-15 % / +10 %
-15 % / +10 %
45 Hz ... 65 Hz
45 Hz ... 65 Hz
120 VA
60 W
20 A / 20 ms
10 A / 20 ms
6 AT
min. 30 ms
min. 300 ms
< 95 V
AC
XAUX (X99):
230 V
AC
120 VA
60 W
6 AT
< 95 V
AC
R310
NTC
F302
3.15 AT
230 V
DC
-15 % / +10 %
-
-
60 W
10 A / 20 ms
6 AT
min. 150 ms
< 140 V
DC
SF_PINF_001_in-output_b.ai
Technical data
65

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dcs880-s series