Xdio: Digital Inputs / Outputs; Xdi: Digital Inputs; Xenc: Encoder; Xtac: Analog Tacho - ABB DCS880 series Hardware Manual

20 ... 5200 a
Hide thumbs Also See for DCS880 series:
Table of Contents

Advertisement

56

XDIO: Digital inputs / outputs

DIO1
Maximum wire size 2.5 mm
As input:
DIO2
+24 V
logic levels: low < 5 V
DC
R
= 2 k
in
Filter: 0.25 ms
As output:
Total output current from +24VD is limited to 200 mA
Filter: 0.04 ms
Parameter settings see

XDI: Digital inputs

DI1
Maximum wire size 2.5 mm
+24 V
logic levels: low < 5 V
DI2
DC
R
= 2 k
DI3
in
Hardware filter: 0.04 ms
DI4
Digital filter up to 8 ms
DI5
DI6
Parameter settings see

XENC: Encoder

A+
OnBoard encoder interface supply voltage 5 V or 24 V (non isolated) depending on J4D
OnBoard encoder interface type differential or single ended depending on J4A ... J4C
A-
Maximum wire size 2.5 mm
B+
B-
Z+
Z-
3
EGND
2
+VENC
100 nF
1
SDCS-CON-H01 ENCODER INPUT A
Parameter settings see

XTAC: Analog tacho

AITACH+
OnBoard tacho interface
Maximum wire size 2.5 mm
AITACH-
Differential input max. voltage 8 ... 270 V
Parameter settings see
Technical data
2
, high > 15 V
DC
DCS880 Firmware Manual Group 11 Standard DIO, FI, FO
2
, high > 15 V
DC
DCS880 Firmware Manual Group 10 Standard DI, RO
2
+5V or +24V
+5V
1k0
4k7
10k
J4A
1k0
4k7
+5V
DCS880 Firmware Manual Group 94 OnBoard speed feedback configuration
2
DCS880 Firmware Manual Group 94 OnBoard speed feedback configuration
3ADW000462R0101 DCS880 Hardware Manual e a
DC
DC

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dcs880-s series

Table of Contents