Cross-Sectional Areas - Tightening Torques - ABB DCS880 series Hardware Manual

20 ... 5200 a
Hide thumbs Also See for DCS880 series:
Table of Contents

Advertisement

34

Cross-sectional areas - Tightening torques

Recommended cross-sectional area to DINVDE 0276-1000 and DINVDE 0100-540
(PE) trefoil arrangement, up to 50°C ambient temperature.
Armature:
Converter type
DCS880-S0x-0025-xx
DCS880-S0x-0050-xx
DCS880-S0x-0075-xx
DCS880-S0x-0100-xx
DCS880-S0x-0150-xx
DCS880-S0x-0200-xx
DCS880-S0x-0250-xx
DCS880-S0x-0300-xx
DCS880-S0x-0320-xx
DCS880-S0x-0350-xx
DCS880-S0x-0450-xx
DCS880-S0x-0520-xx
DCS880-S0x-0650-xx
DCS880-S0x-0680-xx
DCS880-S0x-0820-xx
DCS880-S0x-1000-xx
You will find instructions on how to calculate the PE conductor's cross-sectional area
in VDE 0100 or in equivalent national standards. We would remind you that power
converters may have a current-limiting effect.
Excitation:
Size
DC output current
max. cross sectional area
min. cross sectional area
Tightening torque
Planning the electrical installation
C1, D1
1
(2.)
I
DC
[A-]
[mm²]
[mm²]
25
1 x 6
-
50
1 x 10
-
75
1 x 25
-
100
1 x 25
-
150
1 x 35
-
200
2 x 35
1 x 95
250
2 x 35
1 x 95
300
2 x 70
1 x 95
320
2 x 70
1 x 95
350
2 x 70
-
450
2 x
95
-
520
2 x
95
-
650
2 x 120
-
680
2 x 120
-
820
2 x 150
-
1000
2 x 185
-
H1
H1
6 A
12 A
6 mm²/ AWG 10 6 mm²/ AWG 10 6 mm²/ AWG 10 6 mm²/ AWG 10 6 mm²/ AWG 10
1 mm²/ AWG 16 2.5 mm²/ AWG 13 4 mm²/ AWG 11
3ADW000462R0101 DCS880 Hardware Manual e a
U1, V1, W1
1
(2.)
Iv
[A~]
[mm²]
[mm²]
21
1 x
4
-
41
1 x
6
-
61
1 x 25
-
82
1 x 25
-
114
1 x 35
-
163
2 x 25
1 x 95
204
2 x 25
1 x 95
220
2 x 50
1 x 95
220
2 x 50
1 x 95
286
2 x 50
367
2 x 95
-
424
2 x 95
-
555
2 x 120
-
555
2 x 120
-
669
2 x 120
-
816
2 x 150
-
H2
H3, H5, H6
18 A
25 A
6 mm²/ AWG 10 6 mm²/ AWG 10
1.5 ... 1.7 Nm
PE
[mm²]
[Nm]
1x 4
1 x M6
6
1x 6
1 x M6
6
1x 16
1 x M6
6
1x 16
1 x M6
6
1x 16
1 x M10
25
1x 25
1 x M10
25
1x 25
1 x M10
25
1x 50
1 x M10
25
1x 50
1 x M10
25
1x 50
1 x M10
25
1x 50
1 x M10
25
1x 50
1 x M10
25
1x120
1 x M12
50
1x120
1 x M12
50
1x120
1 x M12
50
1x150
1 x M12
50
H4
DCF803-0035
30 A
6 mm²/ AWG 10
6 mm²/ AWG 10
35 A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dcs880-s series