Control Circuit Terminals On The Sdcs-Con-H01; Recommended Wire Size - Tightening Torques; Control Cables - ABB DCS880 series Hardware Manual

20 ... 5200 a
Hide thumbs Also See for DCS880 series:
Table of Contents

Advertisement

Control circuit terminals on the SDCS-CON-H01

The control circuit terminals are common for all sizes H1 ... H8.
Location of the control circuit board SDCS-CON-H01
The SDCS-CON-H01 is mounted on an electronic tray. The electronic tray is attached in the housing by
means of two hinges.
Watchdog function
The SDCS-CON-H01 has an internal watchdog. The watchdog controls the proper function of the
SDCS-CON-H01 and the firmware. If the watchdog trips, it has the following effects:
– the thyristor firing control is reset and disabled
– all DI's will not be processed
– all DO's are frozen in the actual state
– all AI's will not be processed
– all programmable AO's are frozen in the actual state

Recommended wire size - Tightening torques

Control cables:

Wire sizes:
0.5 ... 2.5 mm
Tightening torques:
2
0.5 Nm (5 lbf·in) for both stranded and solid wiring
(24 ... 12 AWG)
3ADW000462R0101 DCS880 Hardware Manual e a