Selecting the control cables

A double shielded twisted pair cable, e.g. JAMAK by NK Cables, Finland must be
used for analog signals and pulse encoder signals. Employ one individually shielded
pair for each signal. Do not use common return for different analog signals.
A double-shielded cable is the best alternative for low voltage digital signals but
single-shielded twisted multi pair cable is also usable.
Pairs should be twisted as close to terminals as possible.
Run analog and digital signals in separate, screened cables.
Relay-controlled signals, providing their voltage does not exceed 48 V, can be run in
the same cables as digital input signals. It is recommended that the relay-controlled
signals be run as twisted pairs too.
Never run 24 V

Control panel cable

The cable connection of the control panel to the DCS880 converter must not exceed
3 meters (10 ft). The cable type tested and approved by ABB is included in the
control panel option kits.
Double shielded twisted
pair cable
and 115 / 230 V
DC
3ADW000462R0101 DCS880 Hardware Manual e a
Single shielded twisted
multi pair cable
signals in the same cable!
AC
Planning the electrical installation