Jumpers and switches

Jumper / switch
Description
J1 (AI1)
Determines whether analog input AI1 is used as a current
or voltage input
J2 (AI2)
Determines whether analog input AI2 is used as a current
or voltage input
J3 (D20)
Drive-to-drive link termination. Must be set to terminated
position when the thyristor power controller is the last unit
on the link
J4A ... J4D (encoder) OnBoard encoder interface
J5 (AO1)
Determines whether analog output AO1 is used as a
current or voltage output
J6 (grounding)
Digital ground selection switch. Determines whether
DICOM is separated from DIOGND (e.g. the common
reference for digital inputs floats).
See
The insulation voltage between them is 50 V.
J7A, J7B
OnBoard encoder interface
Technical data
Ground isolation diagram.
3ADW000462R0101 DCS880 Hardware Manual e a
Positions
Current (I)
Voltage (U), default
Current (I)
Voltage (U), default
Bus is not terminated,
default
Bus is terminated
J4
J4
A
B
C
D
10 k
pull up
120
differential
default
Feedback
OnBoard Encoder
+ A -
+ B - + Z -
XENC
1
2
3
4
5
Voltage (U), default
Current (I)
DIOGND and DICOM sepa-
rated
DIOGND and DICOM con-
nected, default
Encoder, default
Not in use for DCS880
Encoder
supply
24 V
5 V
default
24 V
5 V
J4D
EGND
6
7
8