4.2.4 Serial connection

This connection is mainly used for the controlled mode or to configure the device.
RS-232
Only point-to-point communication is possible when using the RS-232 interface.
Never connect multiple DLS-C(H)/FLS-C(H)s on a RS-232 serial line
RS-422
It is possible to connect multiple devices on a single RS-422 line. To ensure proper operation, strict Master-Slave communication must be
applied. It is important, that the Master has full control of the communication and never initiates a new communication before termination
of the previous communication (answer from the DLS-C(H)/FLS-C(H) or timeout).
For RS-422 connections, use shielded twisted pair cables only! For detailed information following the RS-422 guidelines.
Fig. 16: Connecting multiple devices with RS-422
Ensure, that all DLS-C(H)/FLS-C(H)s are set to different ID numbers.
The RS-422 interface cannot be used simultaneous with the SSI interface.
Distance Laser Sensor
M
EFERENCE
ANUAL
Tx
Host
(PC or PLC)
Rx
Fig. 15 Point-to-point connection with RS-232
DLS-C(H) / FLS-C(H)
ID switch
Position 0
Host
R
t
(PC or PLC)
(master)
R
t
9..30VDC
24..30VDC with Heating
0V
Rx
1
Tx
2
V+
9..30VDC
7,8
24..30VDC with Heating
14,15
0V
DLS-C(H) / FLS-C(H)
(slave)
(slave)
ID switch
Position 1
DLS-C(H)
DLS-B(H)
FLS-C(H)
DLS-C(H) / FLS-C(H)
(slave)
ID switch
Position 9
R
R
t
t
Page 18/53