Running Time Over And Power-On Time Over Signals (Rnt And Ont) - Hitachi NES1-004SB Quick Reference Manual

Ne-s1 series
Table of Contents

Advertisement

Chapter 7 Explanation of Functions
7.8.10 Running time over and power-on time over signals (RNT and ONT) [b034]
The inverter outputs the operation time over (RNT) signal or the plug-in time over (ONT) signal when the
time specified as the run/power-on warning time (b034) is exceeded.
Item
Run/power-on warning time
(1) Operation time over (RNT) signal
To use this signal function, assign function "11" (RNT) to one of the intelligent output terminals [11] (C021)
and the alarm relay terminal (C026).
Specify the run/power-on warning time (b034).
(2) Plug-in time over (ONT) signal
To use this signal function, assign function "12" (ONT) to one of the intelligent output terminals [11] (C021)
and the alarm relay terminal (C026).
Specify the run/power-on warning time (b034).
7.8.11 0Hz speed detection signal (ZS)
The inverter outputs the 0 Hz speed detection signal when the inverter output frequency falls below the
threshold frequency specified as the zero speed detection level (C063).
To use this signal function, assign function "21" (ZS) to one of the intelligent output terminals [11] (C021)
and the alarm relay terminal (C026).
Item
Zero speed detection level
Output frequency
ZS output
FW
Function code
Range of data
1. to 9999.
b034
1000 to 6553
Function code
C063
C063
ON
ON
7 - 70
0.
Disabling the signal output
Setting in units of 10 hours
(range: 10 to 99,990 hours)
Setting in units of 100 hours
(range: 100,000 to 655,300 hours)
Data or range of data
0.00 to 100.0 (Hz)
ON
Description
Description
Setting of the frequency to be
determined as 0 Hz