Func.
Name
Code
C001
Input [1] function
C002
Input [2] function
C003
Input [3] function
C004
Input [4] function
C005
Input [5] function
Input [1] active
C011
state
Input [2] active
C012
state
Input [3] active
C013
state
Input [4] active
C014
state
Input [5] active
C015
state
Output [11]
C021
function
Alarm relay
C026
function
[FM] terminal
selection
C027
(Pulse/PWM
output)
Digital current
C030
monitor reference
value
Output [11] active
C031
state
Alarm relay active
C036
state
Output mode of
C038
low current
detection
Low current
C039
detection level
Output mode of
C040
overload warning
Overload warning
C041
level
"C" Function
Description
Select input terminal [1] function, 34
options (see next section)
Select input terminal [2] function, 34
options (see next section)
Select input terminal [3] function, 34
options (see next section)
Select input terminal [4] function, 34
options (see next section)
Select input terminal [5] function, 34
options (see next section)
Select logic conversion, two option
codes:
00normally open [NO]
01normally closed [NC]
27 programmable functions available for
logic (discrete) outputs
(see next section)
27 programmable functions available for
logic (discrete) outputs
(see next section)
9 programmable functions:
00Output frequency (PWM)
01Output current (PWM)
03Output frequency (Pulse train)
04Output voltage (PWM)
05Input power (PWM)
06Electronic thermal load ratio (PWM)
07LAD frequency (PWM)
08Output current (Pulse train)
10Heat sink temperature (PWM)
Current with digital current monitor
output at 1,440Hz
Range is 20%~200% of rated current
Select logic conversion, two option
codes:
00normally open [NO]
01normally closed [NC]
Two option codes:
00During acceleration, deceleration
and constant speed
01During constant speed only
Set the level of low load detection, range
is 0.00 to 2.00*inverter rated current
Two option codes:
00During accel., decel. and constant
speed
01During constant speed only
Sets the overload warning signal level
between 0% and 200% (from 0 to two
time the rated current of the inverter)
13 - 19
Chapter 13 Option
Defaults
Run
Initial data
Initial data
Mode
standard
CHN
Edit
200/400
200/400
00
[FW]
01
[RV]
02
[CF1]
03
[CF2]
18
[RS]
00
00
00
00
00
01
[FA1]
05
[AL]
07
Rated
current
00
01
01
Rated
current
01
Rated
current
x 1.15
Initial data
EU
Units
200/400