Energy-Saver Operation (A085,A086); Stabilization Constant Setting (H006/H206,A045,B083) - Hitachi NES1-004SB Quick Reference Manual

Ne-s1 series
Table of Contents

Advertisement

7.5.19 Energy-saver operation [A085/A086]
The energy-saver operation function allows you to automatically minimize the inverter output power while
the inverter is driving the motor at constant speed. This function is suited to operating a fan, pump, or other
load that has a reduced-torque characteristic.
To use this function, specify "01" for the operation mode selection (A085).
Use the energy saving mode tuning function (A086) to adjust the response and accuracy of the
energy-saver operation.
The energy-saver operation function controls the inverter operation comparatively slowly. Therefore, if a
sudden change in the load occurs (e.g., impact load is applied), the motor may stall, and, consequently,
the inverter may trip because of overcurrent.
Item
Operation mode selection
Item
Energy saving mode tuning
7.5.20 Stabilization constant setting
The stabilization constant setting function allows you to adjust the inverter to stabilize the motor operation
when the motor operation is unstable.
If the motor operation is unstable, check the motor capacity setting (H003/H203) and motor pole setting
(H004/H204) to determine whether the settings match the motor specifications. If they do not match,
readjust the settings. If the primary resistance of the motor is less than the standard motor specification, try
to increase the setting of "H006/H206 " step by step. Try to reduce the setting of "H006/H206 " if the
inverter is driving a motor of which the capacity is higher than the inverter rating.
You can also use the following methods to stabilize the motor operation:
1) Reducing the carrier frequency (b083)
2) Reducing the V/f gain setting (A045)
Item
Stabilization constant
V/f gain setting
Carrier frequency setting
Function code
A085
Function code
A086
Function code
H006/H206
A045/A245
20. to 100. (%)
b083
2.0 to 15.0 (kHz)
7 - 39
Chapter 7 Explanation of Functions
Data
00
Normal operation
01
Energy-saving operation
Data
Response
0
100
Data
Increase or reduce the setting to stabilize
0. to 255.
the motor.
Reduce the setting to stabilize the motor.
Reduce the setting to stabilize the motor.
Description
Accuracy
Slow
High
Quick
Low
Description