Connection example diagram and timing for commercial power source switching running

CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Mg
R(L1)
(T1)U
S(L2)
(T2)V
T(L3)
(T3)W
H
O
L
FWY
AL1
FW
AL2
RV
RVY
AL0
CS
CSY
CM1
ON
Mg1 and Mg2 interlocking time
ON
Set time by timer 2C
(The time is generally set to 1 to 3 seconds. Error may come when the set time is 4 seconds or more.)
ON
OFF
20 ms or more
ON
[F-22] IPS WAIT
Running
Mg1
THRY
IM
Mg2
NOTE 1: When the ELB trips due to a ground-fault, the commercial power
source circuit will not operate. Therefore, when a backup is
necessary, take a commercial power source circuit from the ELBC.
NOTE 2: Use weak current relays for FWY, RVY, and CSY. Separate AC
relays from DC relays. The above sequence is a reference drawing
for timing.