Chapter 13 Option
Func.
Name
Code
A076
PV source
Reverse
A077
PID action
PID
A078
variation
range
AVR
A081
function
select
AVR
function
A281
select,
nd
2
motor
AVR
A082
voltage
select
AVR
voltage
A282
select,
nd
2
motor
AVR filter
A083
time
constant
AVR
A084
deceleratio
n gain
Energy-sav
ing
A085
operation
mode
Energy-sav
A086
ing mode
tuning
Acceleratio
A092
n time (2)
Acceleratio
A292
n time (2),
nd
2
motor
Deceleratio
A093
n time (2)
Deceleratio
A293
n time (2),
nd
2
motor
Select
method to
A094
switch to
Acc2/Dec2
profile
Select
method to
switch to
A294
Acc2/Dec2
nd
profile, 2
motor
"A" Function
Description
Selects source of Process Variable (PV),
option codes:
01[O/OI] terminal
02Modbus network
10Calculate function output
Two option codes:
00PID input = SP-PV
01PID input = -(SP-PV)
Sets the limit of PID output as percent of
full scale,
range is 0.0 to 100.0%
Automatic (output) voltage regulation,
selects from three type of AVR functions,
three option codes:
00AVR enabled
01AVR disabled
02AVR enabled except during
deceleration
200V class inverter settings:
200/215/220/230/240
400V class inverter settings:
380/400/415/440/460/480
Define the time constant of the AVR filter,
range is 0.000 to 1.000 seconds.
Gain adjustment of the braking
performance, range is 50 to 200%
Two option codes:
00Normal operation
01Energy-saving operation
Range is 0.0 to 100.0 %.
nd
Duration of 2
segment of acceleration,
range is:
0.00 to 3600.00 seconds.
nd
Duration of 2
segment of deceleration,
range is:
0.00 to 3600.00 seconds.
Three options for switching from 1st to
2nd accel/decel:
00
2CH input from terminal
01
Transition frequency
02
Forward and reverse
Run
Initial data
Mode
standard
Edit
13 - 8
Defaults
Initial data
Initial data
CHN
200/400
200/400
200/400
01
←
←
00
←
←
0.0
←
←
02
01
02
02
01
02
200/
220/
230/
400
380
400
200/
220/
230/
400
380
400
0.030
←
←
100.
←
←
00
←
←
50.0
←
←
10.00
←
←
10.00
←
←
10.00
←
←
10.00
←
←
00
←
←
00
←
←
EU
Units
%
V
V
s
%
%
s
s
s
s