Hitachi NES1-004SB Quick Reference Manual page 265

Ne-s1 series
Table of Contents

Advertisement

Chapter 13 Option
Func.
Code
(WOP)
b001
Restart mode on
(Restart
power failure /
under-voltage trip
mode UV)
b002
(Allowable
under-voltage power
UV time)
b003
Retry wait time
(Retry wait
before motor restart
time UV)
Instantaneous power
b004
(UV trip on
under-voltage trip
stop)
alarm enable
Number of restarts
b005
on power failure /
(No. of restart
under-voltage trip
UV)
b007
Restart frequency
(Restart
min.FQ)
"b" Function
Name
Select inverter restart
Four option codes:
00Alarm output after
trip, no automatic restart
01Restart at 0Hz
02Resume operation
after frequency matching
03Resume previous
freq. after freq. matching,
then decelerate to stop
and display trip info
The amount of time a
under-voltage can occur
without tripping the power
Allowable
failure alarm. Range is
0.3 to 25.0 sec. If
failure time
under-voltage exists
longer than this time, the
inverter trips, even if the
restart mode is selected.
Time delay after
under-voltage condition
goes away, before the
inverter runs motor again.
Range is 0.3 to 100.0
Three option codes:
failure /
02Disable during stop
and decelerates to a stop
Two option codes:
00Restart 16 times
01Always restart
events
Restart the motor from
0Hz if the frequency
becomes less than this
threshold
set value during the motor
is coasting, range is 0.00
Run
Mode
Description
Edit
method,
power input
seconds.
00Disable
01Enable
to 400.00Hz
13 - 36
Defaults
Initial data
Initial data
Initial data
standard
CHN
EU
200/400
200/400
200/400
00
1.0
1.0
00
00
0.50
Unit
s
s
s
Hz

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents