Cable types and lengths

Double-shielded twisted-pair cable is recommended.
Maximum cable lengths:
30 m (100 ft) between activation switch [K] and inverter control unit.
60 m (200 ft) between multiple inverter units
60 m (200 ft) between external power supply and first inverter unit
With frame n×R8i inverter units: 30 m (100 ft) between BCU control unit and last
inverter module in the chain.
Note: The voltage at the INx terminals of each inverter control unit (or frame R8i inverter
module) must be at least 17 V DC to be interpreted as "1".

Grounding of protective shields

Ground the shield in the cabling between the activation switch and the control unit at
the control unit.
Ground the shield in the cabling between two control units at one control unit only.
For frame R8i and multiples: Do not ground the shield in the cabling between BCU and
R8i module, or between R8i modules.
The Safe torque off function 311