Cable types and lengths
•
Double-shielded twisted-pair cable is recommended.
•
Maximum cable lengths:
•
30 m (100 ft) between activation switch [K] and inverter control unit.
•
60 m (200 ft) between multiple inverter units
•
60 m (200 ft) between external power supply and first inverter unit
•
With frame n×R8i inverter units: 30 m (100 ft) between BCU control unit and last
inverter module in the chain.
Note: The voltage at the INx terminals of each inverter control unit (or frame R8i inverter
module) must be at least 17 V DC to be interpreted as "1".
Grounding of protective shields
•
Ground the shield in the cabling between the activation switch and the control unit at
the control unit.
•
Ground the shield in the cabling between two control units at one control unit only.
•
For frame R8i and multiples: Do not ground the shield in the cabling between BCU and
R8i module, or between R8i modules.