Connecting the control cables – All frame sizes
For technical data and default I/O connections of the inverter control unit, refer to chapter
The inverter control unit
1. In the cabinet, remove shrouding wherever necessary to allow access to the cable
entries and any trunking inside the cubicle.
2. Run the control cables into the cubicle. If possible, arrange for a 360° grounding of the
cable shield at the cable entry.
If the outer surface of the shield is non-conductive, turn the shield inside out as shown
below and wrap copper foil around the cable to keep the shielding continuous. Do not
cut the grounding wire (if present).
Stripped cable
Cable shield
3. Run the cables to the control unit of the inverter (or other connection point) using cable
trunking wherever possible.
4. (Only when running the cable to the inverter module) The inverter control units have a
clamp plate attached. Remove the outer sheathing of the cable at one of the clamps
on the plate. Tighten the clamp onto the bare cable shield.
5. Cut the cables to suitable length.
(page 293).
Conductive surface of
the shield exposed
Electrical installation 159
Stripped part covered
with copper foil
Copper foil
Shielded twisted pair
Grounding wire