Cable Types And Lengths; Grounding Of Protective Shields; Single Inverter Unit (Internal Power Supply); Dual-Channel Connection - ABB ACS880-107 Hardware Manual

Inverter units
Hide thumbs Also See for ACS880-107:
Table of Contents

Advertisement

Cable types and lengths

Double-shielded twisted-pair cable is recommended.
Maximum cable lengths:
30 m (100 ft) between activation switch [K] and inverter control unit
60 m (200 ft) between multiple inverter units
60 m (200 ft) between external power supply and first inverter unit
With frame n×R8i inverter units: 30 m (100 ft) between BCU control unit and last
inverter module in the chain.
Note: The voltage at the INx terminals of each inverter control unit (or frame R8i inverter
module) must be at least 17 V DC to be interpreted as "1".

Grounding of protective shields

Ground the shield in the cabling between the activation switch and the control unit at
the control unit.
Ground the shield in the cabling between two control units at one control unit only.
For frame R8i and multiples: Do not ground the shield in the cabling between BCU and
R8i module, or between R8i modules.

Single inverter unit (internal power supply)

Dual-channel connection

Inverter unit
Control unit
Control logic
OUT1
+24 V
SGND
IN1
IN2
UDC+
A
UDC–
The Safe torque off function 159
T1/U, T2/V, T3/W
K

Advertisement

Table of Contents
loading

Table of Contents