Air temperature
Relative humidity
Contamination
Chemical gases
Solid particles
Vibration
IEC 61800-5-1
IEC 60068-2-6:2007,
EN 60068-2-6:2008
Environmental testing Part 2:
Tests -Test Fc: Vibration
(sinusoidal)
Shock
IEC 60068-2-27:2008,
EN 60068-2-27:2009
Environmental testing - Part
2-27: Tests - Test Ea and
guidance: Shock

Materials

Module housing
Package
0 ... +40 °C
(+32 ... +104 °F). No
condensation allowed.
Output derated in the
range +40 ... +50 °C
(+104 ... +122 °F). See
section
Ambient
temperature derating
(page 280).
5 to 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the
presence of corrosive gases.
IEC/EN 60721-3-
3:2002: Classification of
environmental
conditions - Part 3-3:
Classification of groups
of environmental
parameters and their
severities - Stationary
use of weather
protected locations
Class 3C2
Class 3S1. No
conductive dust allowed.
10...57 Hz: max.
0.075 mm amplitude
58...150 Hz: 1 g
Tested in ABB multidrive
cabinet (ACS880-x07)
according to:
Max. 1 mm (0.04 in.)
(5 ... 13.2 Hz),
max. 0.7 g
(13.2 ... 100 Hz)
sinusoidal
Not allowed
PC/ABS 3 mm, color NCS 1502-Y (RAL 9002 / PMS 1C Cool Gray) and RAL
9017 (frames R1i...R5i)
PC+10%GF 3.0mm, Color RAL 9017 (in frames R1i...R3i only)
Hot-dip zinc coated steel sheet 1.5 to 3.0 mm, thickness of coating 20
micrometers, color NCS 1502-Y
Frames R1i...R5i: Corrugated cardboard. Foam cushions: PP-E. Plastic
wrapping: PE-LD. Strapping: PP.
Frames R6i and up: Plywood base, corrugated cardboard, PET straps.
-40 to +70 °C
(-40 to +158 °F)
Max. 95%
IEC 60721-3-1
Class 1C2
Class 1S3 (packing
must support this,
otherwise 1S2)
For modules and
cabinets in packages:
IEC/EN 60721-3-1:1997
Classification of
environmental
conditions - Part 3:
Classification of groups
of environmental
parameters and their
severities - Section 1:
Storage
With packing max.
2
2
100 m/s
(330 ft./s
)
11 ms
Technical data 287
-40 to +70 °C
(-40 to +158 °F)
Max. 95%
IEC 60721-3-2
Class 2C2
Class 2S2
For cabinet package:
IEC/EN 60721-3-1:1997
Classification of
environmental
conditions - Part 3:
Classification of groups
of environmental
parameters and their
severities - Section 2:
Transportation
With packing max.
2
2
100 m/s
(330 ft./s
)
11 ms