Derating; Ambient Temperature Derating; Altitude Derating; Switching Frequency Derating - ABB ACS880-104 Hardware Manual

Hide thumbs Also See for ACS880-104:
Table of Contents

Advertisement

280 Technical data

Derating

Ambient temperature derating

In the temperature range +40...50 °C (+104...122 °F), the rated output current is derated
by 1% for every added 1 °C (1.8 °F). The output current can be calculated by multiplying
the current given in the rating table by the derating factor (k):
k
1.00
0.90
0.80
+40 °C
+104 °F

Altitude derating

At altitudes from 1000 to 4000 m (3300 to 13123 ft) above sea level, the continuous output
currents given above must be derated 1% for every 100 m (328 ft). For a more accurate
derating, use the DriveSize PC tool.

Switching frequency derating

Switching frequencies other than default can require output current derating. Contact ABB
for more information.

Output frequency derating

Motor operation above 150 Hz can require type-specific output current derating. Contact
ABB for more information.

Cooling characteristics, noise, DC capacitance

Inverter unit type
ACS880-104-...
U
= 400 V
N
004A8-3
006A0-3
008A0-3
0011A-3
0014A-3
0018A-3
0025A-3
0035A-3
0044A-3
0050A-3
0061A-3
0078A-3
0094A-3
0100A-3
0140A-3
0170A-3
0210A-3
0250A-3
T
+50 °C
+122 °F
Power loss
Air flow
3
W
m
/h
70
24
80
24
90
24
110
48
140
48
170
48
200
142
300
142
350
200
410
200
500
290
600
290
740
290
750
290
1100
650
1400
650
1800
650
2000
650
Noise level
3
dB(A)
ft
/min
14
47
14
47
14
47
28
39
28
39
28
39
84
63
84
63
118
71
118
71
171
70
171
70
171
70
171
70
383
71
383
71
383
71
383
71
DC
capacitance
µF
280
280
280
435
865
865
785
785
1178
1178
1570
2355
2355
2355
4500
4500
4500
6750

Hide quick links:

Advertisement

Table of Contents
loading