Input power (DC) connection

Voltage (U
)
1
Drive AC supply network
type
Input terminals

Motor (AC) connection

Motor types
Voltage (U
)
2
Frequency
Current
Switching frequency
Maximum motor cable
length
ACS880-104-xxxxx-3: 513...566 V DC. This is indicated in the type
designation label as typical input voltage level (566 V DC).
ACS880-104-xxxxx-5: 513...707 V DC. This is indicated in the type
designation label as typical input voltage levels (566/679/707 V DC).
ACS880-104-xxxxx-7: 709...976 V DC. This is indicated in the type
designation label as typical input voltage levels (742/849/976 V DC).
TN (grounded) and IT (ungrounded) systems, corner-grounded systems up
to 600 V AC
Frame R1i
UDC+, UDC–: 0.25...4 mm
PE: 1.5 N·m (13 lbf·in)
Frame R2i
UDC+, UDC–: 0.5 ... 6 mm
PE: 1.5 N·m (13 lbf·in)
Frames R3i, R4i and R5i
UDC+, UDC–: 6...70 mm
post torque 4 N·m (30 lbf·in). Other conductor sizes can be used by
replacing the original lug with a suitable crimp ring terminal.
PE: Screw size M5, torque 3 N·m (25 lbf·in)
Connector cover screws: Torque 3 N·m (25 lbf·in)
Frames R6i and R7i
See chapter
Dimension drawings
module in a 400 mm wide Rittal TS 8 enclosure
Frame R8i and multiples
M12, maximum intrusion into module 20 mm (0.8"). See also chapter
Dimension drawings
(page 335), and section
wide Rittal TS 8 enclosure
Asynchronous AC induction motors, permanent magnet synchronous motors
and AC induction servomotors
0 to AC supply voltage of drive, 3-phase symmetrical, U
weakening point
0...±598 Hz, except
0...±120 Hz for frames R1i...R5i with output (du/dt) filters
0...±200 Hz for frames R6i and R7i with output (du/dt) filters
• For higher operational output frequencies, please contact your local ABB
representative.
• Operation above 150 Hz may require type-specific derating. For more
information, contact your local ABB representative.
See section
Ratings
(page 277).
Frames R1i...R4i: 4.5 kHz (typical)
Frames R5i...R8i: 3 kHz (typical)
The switching frequency can vary per frame and voltage. For exact values,
please contact your local ABB representative.
Frames R1i...R2i: 150 m (492 ft)
Frames R3i...R7i: 300 m (984 ft)
Note: Tested with 100 m (328 ft) for EMC Category C3. See standards and
markings information in Electrical planning instructions for ACS880
multidrive cabinets and modules (3AUA0000102324 [English]).
Frame R8i and multiples: 500 m (1640 ft)
2
, 0.5 ... 0.6 N·m (4.4 ...5.3 lbf·in)
2
, 1.2 ... 1.5 N·m (10.6 ... 13.3 lbf·in)
2
. Allen screw torque 15 N·m (11 lbf·ft), connection
(page 335), and section
(page 99)
One R8i module in a 400 mm
(page 112)
Technical data 285
One R6i/R7i
at field
max