46 Electrical installation
Connecting the control cables
Default I/O connection diagram
Terminal
Type
+
+24 V DC
-
0 V DC
1
User DI1
2
User DI2
3
User DI3
4
User DI4
5
User DI5
X2
6
User DI6
7
User DI7
8
User RO1
9
User AI2
10 User AI2
11 User AI3
12 User AI3
You can freely configure the I/O signals with different fault names and reactions. Refer to
the PVS800-57B central inverters firmware manual (3AXD50000048332 [EN]).
Connection procedure
360-degree grounding at the cabinet lead-through for the control cables:
Make sure that a proper environmental seal remains after the installation.
1. Cut adequate holes in the rubber grommets in the lead-through plate.
2. Put the cables through the grommets into the cabinet.
3. Strip the plastic sheath of the cable above the lead-through plate just enough to
ensure proper connection of the bare shield.
2
3
a
1
Note: If the outer surface of the shield is non-conductive:
•
Cut the shield at the midpoint of the bare part. Do not cut the conductors or the
grounding wire (if present).
•
Turn the shield inside out to expose its conductive surface.
•
Cover the turned shield and the stripped cable with copper foil to make the shielding
continuous.
Control I/O connection diagram
Rating
+24 V DC
0 V DC
24 V DC
24 V DC
24 V DC
24 V DC
24 V DC
24 V DC
24 V DC
24 V DC
4–20 mA
4–20 mA
Side view of the cable lead-through
b
a) Grommet
b) EMI conductive cushion
c) Lead-through plate
c
Functionality
Power distribution
Power distribution
+
-
+
-