Commissioning
7
Commissioning
7.1
TZIDC-200
bieten
1. Feed in pneumatic auxiliary power.
2. Feed in electrical supply power.
•
3. Check mount:
•
•
4. Run Autoadjust.
For linear actuators
•
•
•
For part-turn actuators
•
•
•
If Autoadjust is successful, the parameters will be stored automatically and the positioner will
revert to operating mode 1.1.
If an error occurs during Autoadjust, the process will be terminated with an error message. If
this happens, press and hold down
to the operating level, mode 1.3 (manual adjustment within the sensor range). The mount is
checked and corrected if necessary. Autoadjust then runs again.
IMPORTANT (NOTE)
Autoadjust does not always result in optimum control conditions.
1)
The zero position is determined automatically and saved during Autoadjust (counter-clockwise (CTCLOCKW) for
linear actuators and clockwise (CLOCKW) for part-turn actuators).
28
Feed in setpoint current 4 ... 20 mA (terminals +11 / -12)
Press and hold
, and press
within the sensor range) is displayed. Release
Press
or
to move the actuator into the mechanical end position; check the end
positions; rotation angle is displayed in degrees; for high-speed mode, press
simultaneously.
Recommended range:
-
between -28 ... 28° for linear actuators
-
between -57 ... 57° for part-turn actuators
Minimum angle: 25°
1)
:
Press and hold
until
Press
again and hold down until the countdown ends.
Release
; this starts Autoadjust.
1)
:
Press and hold
Press
again and hold it down until the countdown ends.
Release
; this starts Autoadjust.
TZIDC-200, TZIDC-210, TZIDC-220
or
until operating mode 1.3 (manual adjustment
is displayed; release the control button.
until
is displayed; release the control button.
or
for approximately three seconds. The unit will switch
.
42/18-85-EN
and