Transmission Data And Influences; Environmental Capabilities; Housing - ABB TZIDC-200 Operating Instructions Manual

Electro-pneumatic positioner. for 4 ... 20 ma two-wire technology, hart, profibus pa, foundation fieldbus
Hide thumbs Also See for TZIDC-200:
Table of Contents

Advertisement

9.2.6

Transmission data and influences

Output Y1
Increasing:
Increasing output signal 0 ... 100 %
Increasing pressure at output Y1
Decreasing:
Increasing output signal 0 ... 100 %
Decreasing pressure at output Y1
Characteristic deviation
Tolerance band
Dead band
Resolution (A/D conversion)
Sample rate
Influence of ambient temperature
Influence of vibration
Seismic requirements
Meets requirements of DIN / IEC 68-3-3 Class III for strong and
strongest earthquakes.
Influence of mounting orientation
Not measurable.
Meets the requirements of the following directives
-
EMC Directive 2014/30/EU
-
EC Directive for CE conformity marking
9.2.7

Environmental capabilities

Ambient temperature
For operation, storage and transport:
When using proximity switches
SJ2-S1N (NO):
Relative humidity
Operational (with closed housing
and air supply switched on):
Transport and storage:
42/18-85-EN
< 0,5 %
0.3 ... 10 %, adjustable
0,1 ... 10 %, adjustable
> 16000 steps
20 ms
< 0.5 % per 10 K
< ± 1 % to 10 g and 80 Hz
-40 ... 85 °C (-40 ... 185 °F)
-25 ... 85 °C (-13 ... 185 °F)
95 % (annual average),
condensation permissible
75 % (annual average), non-
condensing
TZIDC-200, TZIDC-210, TZIDC-220
9.2.8

Housing

Material / Degree of protection
Aluminum, protection class IP 65 (optional IP 66) / NEMA 4X
Surface / Color
Electrostatic dipping varnish with epoxy resin, stove-hardened. Case
varnished black, RAL 9005, matte, housing cover Pantone 420.
Electrical connections
Screw terminals:
Max. 1.0 mm
Max. 2.5 mm
IMPORTANT (NOTE)
Do not expose the terminals to strain.
Four thread combinations for cable entry and pneumatic
connection
- Cable: thread 1/2-14NPT, air pipe: thread 1/4-18 NPT
- Cable: thread M20 x 1,5, air pipe: thread 1/4-18 NPT
- Cable: thread M20 x 1,5, air pipe: thread G 1/4
- Cable: thread G 1/2, air pipe: thread Rc 1/4
(Optional: With cable gland(s) and pipe plugs if necessary)
Weight
3,0 kg (1,36 lb)
Mounting orientation
Any
Dimensions
See "Dimensions"
Specifications
2
(AWG 17) for options
2
(14 AWG) for bus connector
43