Commissioning; Checks Prior To Commissioning; Mechanical Mounting Checks; Moving To End Positions Following Completion Of Auto Adjust - ABB VAC D500 Commissioning Instructions

Electro-pneumatic positioner
Table of Contents

Advertisement

6

Commissioning

hange from one to two columns
During commissioning, the mechanical mounting on the linear
and part-turn actuators is checked. For this purpose, the
actuator is first moved into the end positions and Auto Adjust
is then carried out.
6.1

Checks prior to commissioning

Air pressure in the compressed air connecting line:
1.4 ... 10 bar (20 ... 145 psi)
Current input active:
4 ... 20 mA
6.2

Mechanical mounting checks

6.2.1
Moving to end positions following completion of
Auto Adjust
Process display
1. Use
to switch to the Operating Mode menu.
Operating Mode
Auto Adjust
O
Adaptive
O
Control
O
Manual SP
O
Manual Sensor
Configuration
Back
2. Use
or
to select the "Manual Sensor" operating
mode.
3. Use
and
to move to the relevant end positions.
-45.0
Pos. Ang.
Check the end positions. The angle of rotation is displayed in
degrees.
Recommended range:
— between -30 ... 30° for linear actuators
— between -45 ... 45° for part-turn actuators
OK
°
6.2.2

Moving to end positions with a new device

Process display
Electronic
1. Use
and
to move to the relevant end positions.
-45.0
Pos. Ang.
Check the end positions. The angle of rotation is displayed in
degrees.
Recommended range:
— between -30 ... 30° for linear actuators
— between -45 ... 45° for part-turn actuators
Auto Adjust must then be performed. The "Starting Auto
Adjust" section describes how Auto Adjust is performed.
°
D500
| CI/EDP300-EN Rev. A 19