9.3

TZIDC-220

9.3.1

Communication

Specification
Physical Layer
Transmission rate
Block types
Block class
Number of linkage objects
Device description (DD)
File
Max. execution time
Supply voltage
Max. permissible voltage
Power consumption
Current in the event of an
error
FF Certification

Device name

Dev. ID
Device address
ATEX certificate for FISCO
Insensitive to reversed
polarity
Class
Factory default
Diagnostic functions
42/18-85-EN
FOUNDATION fieldbus, version 1.5
Model 113, 121 (IEC 61158-2)
31.25 Kbit/s
1 AO Function block
1 PID block
1 Resource block
1 Transducer block
1 physical block
AO block: standard
PID block: enhanced
Resource block: enhanced
Transducer block: custom
22
Rev. No. 1 (file name 0201.ffo,
0201.sym)
Common file format (file name:
020101.cff)
AO block: 40 milliseconds
PID block: 50 milliseconds
Power feed from the fieldbus
9.0 ... c 32.0 V DC
35 V DC
11.5 mA
15 mA (11.5 mA + 3.5 mA)
Registered with ITK 4.51, Dec.2003
IT Camp. Number IT023200
ABB TZIDC-200, TZIDC-210,
TZIDC-220-TAG
0003200028-TZIDC-200, TZIDC-
210, TZIDC-220XXXXXXXXXX
Between 10 and 247, default
address 23
Yes
Yes
LM profile 32L, 31 PS
The positioner is not delivered in an
aligned state. To adjust the
operating range and control
parameters, an automatic
configuration must be run on the
unit. Otherwise, the transducer block
remains in out-of-service mode.
Self-diagnostics for the positioner
hardware and software, valve
diagnostics with enhanced alarm
handling
TZIDC-200, TZIDC-210, TZIDC-220
9.3.2
Device name
Device name
ABB TZID-C220XXXXXXXXXX
Dev. ID
0X3200028-TZID-C220XXXXXXXXXXX
9.3.3

Output

Range
Air capacity
at 1.4 bar (20 psi)
supply pressure
at 6 bar (90 psi)
supply pressure
Output function
Shut-off values
9.3.4

Travel

Ste
Rotation angle
Used range
25 ... 120°
rotary actuators, optionally 270°
25 ... 60°
linear actuators
Travel time
prolongation
Setting range
0 ... 200 seconds, separately for each
direction
9.3.5

Air supply

Instrument air
Supply pressure
IMPORTANT (NOTE)
Do not exceed the maximum operating pressure of the
actuator!
Air consumption
Specifications
0 ...6 bar (0 ... 90 psi)
3
5.0 kg/h = 3.9 Nm
/h=2.3 scfm
3
13 kg/h = 10 Nm
/h = 6.0 scfm
For single or double-acting actuators,
air is vented from actuator or actuator
is blocked in case of (electrical) power
failure
End Position 0 %
= 0 ... 45 %
End position 100 % = 55 ... 100 %
free of oil, water and dust acc. to
DIN / ISO 8573-1
pollution and oil content according to
Class 3 (purity: max. particle size:
5 µm, max. particle density:
3
5 mg / m
; oil content: max.
3
concentration: 1 mg / m
; pressure
dew point: 10 K below operating
temperature
1.4 ... 6 bar (20 ... 90 psi)
< 0.1 kg/h / 0.05 scfm (independent
of supply pressure)